Profibus PA Marin

Profibus PA Marin SHF1

Variant:

PA BUS,  IEC 61158-2, specifically used to connect sensors / actuators in the Process Automation (PA).  Suitable for use in ship- and offshore applications, as well in the industry. Low smoke and halogen free. Highly flexible 1 mm² (32 x 0,2 mm).

Construction

Conductor
1.0 [mm²]
Flexible
bare or tinned Cu
class 5
32 x 0,20 mm
IEC 228
Insulation
Foamskin PE
Nom. 2.60 [mm]
No. of pairs
1
Colour code
Red, green
Separator
Plastfoil
+ filler
Screen
Tinned Cu-braid
≥85 [% optical cover]
Jacket
Black
SHF1
LSZH
O.D.
7.9 ± 0.2 [mm]
Weight
90 [kg/km]
Jacket marking
NEK Kabel - Marin - cable - Profibus PA - 1x2x1.00mm² -
 SHF1 - ****m - DD/MM/YY

Specifications

Operating temperature normal
-30 – +70 [°C]
Temperature @ installation
-10 – +50 [°C]
Operating voltage
125
[V]
Test Voltage
1
[kV-DC]
Loop Resistance / Inductance Ratio
≤ 44
Ω/km
Screen resistance
< 9.5
[mΩ/m]
Characteristic impedance
100 ± 20 [Ω @ 100 MHz]
Insulation resistance
≥ 1 [GΩ x km]
Transfer impedance
< 20 [mΩ/m]
@10MHz
Tensile strength
100
[N]
Capacitance
Nom. 50 [pF/m @ 800-1000Hz]
Attenuation
≤ 3.0 dB/100 m at 39 kHz
≤ 6.5 dB/100 m at 100 kHz
≤ 12.0 dB/100 m at 1 MHz
Min. bending radius flexible
12 [x outer diam]
Min. bending radius installed
6 [x outer diam]

Norms

Halogenfree, max content corrosive and toxic gases
IEC 60754-1 and IEC 60754-2
EN 50267
Material properties, insulation and sheath
IEC 60092-360
3582
Design and testing standards
IEC 61158-2
EN 50170
Flame resistance
IEC 60332-3-22 Cat.A
Flame retardant
IEC 60332-1-2
Ozone resistant
300h
Smoke emission
IEC 61034
Oil and fuel resistant
IEC 60811-2-1
IRM 902
23ºC / 7 days, 70°C / 4h
Part No.
1091144 bare Cu-conductors
3010008 tinned Cu-conductors
Also available with SHF2 jacket

Updated

Date Rev. Description
05.04.2019 1 DNV Approved
04.06.2019 2 Additional information