Shielded BUS-cable, IEC 61158-2, certified for use in ship- and offshore installations. The cable is low smoke and zero halogen,
oil- and UV-resistant, AWG 22/7 tinned Cu-conductor, foam PE insulation, filler, AL/Mylar and tinned CU-braid screen, outer jacket SHF1. The cable has increased elctromagnetic compability (EMC) requirments.
Construction
Conductor
Stranded
tinned Cu
7 x 0,254 [mm]
AWG 22/7
(0.35mm²)
Insulation
Foamskin PE
Ø=2,55±0,05 [mm]
Screen
Collective
Al/Mylar
Colour code
Red, green
Filler
PP
Screen
Al/Mylar
100 [% coverage]
Screen 2
Tinned Cu braid
60 [% optical coverage]
Jacket
SHF1
O.D.
7,8 [mm]
Weight
80 [kg/km]
Jacket marking
NEK Kabel - Profibus DP Marin - 1x2xAWG22/7 SHF1 - DNV-GL / RS - IEC 60332-3-22 - batch no - <****meter> - <dd/mm/yyyy>
Specifications
Operating temperature normal
-40 - +80 [°C]
Temperature @ installation
-20 - +60 [°C]
Operating voltage
100
[V]
Test Voltage
1
[kV-DC]
Conductor resistance
≤55 [Ω/km]
Insulation resistance
≥1 [GΩ x km]
Capacitance
30 [pF/m]
at 1kHz
Attenuation
≤45dB/km @ 16MHz ≤22dB/km @ 4MHz ≤5dB/km @ 38.4KHz ≤3dB/km @ 9.6KHz
Min. bending radius flexible
20 [x outer diam]
Min. bending radius installed
10 [x outer diam]
Norms
Halogenfree, max content corrosive and toxic gases
IEC 60754-1 & IEC 60754-2
Material properties, insulation and sheath
IEC 60092-360
Design and testing standards
IEC 61158-2
IEC 60092-360
Flame resistance
IEC 60332-3-22 Cat.A
Flame retardant
IEC 60332-1
Smoke emission
IEC 61034-2
Field bus specifications
IEC 61784 - 1 - 2
IEC 61158 ed. 6
UV-resistant
UL 1581 (300H)
Certification
DNV / RS
Part No.
Black: 1091092 Blue: 3010005 Purple: 3010006
Updated
Date | Rev. | Description |
---|---|---|
5.4.2019 | 1 | DNV-GL Approved |
15.4.2019 | 2 | Additional information |
24.05.2019 | 3 | Adding part numbers |
24.08.2020 | 4 | Temp.range |