120 Ω Armoured BUS cable for industrial- and offshore environments. Tape and braided copper screens.
Data transmission in industrial environments.
Construction
Conductor
0.35 [mm²]
stranded
tinned Cu
AWG 22/7
(7 x 0.254 mm)
Insulation
Foam PE
Ø = 1.75 [mm]
Colour code
White, yellow, blue and orange
Screen
Al/Mylar
Screen 2
Tinned Cu braid
≥ 85 [% optical coverage]
Inner jacket
SHF1
Ø = 6.6 ± 0.3 [mm]
Armour alt.1
Galvanised steel wire braid
0.3 [mm]
Armour alt.2
Tinned Cu-braid
0.3 [mm]
Outer Jacket
Black or green
SHF1
thicknes app. 1.00 [mm]
O.D.
9.8 ± 0.50 [mm]
Jacket marking
NEK Kabel – RS485 Industrial BUS – nx2xAWG22/7 – GSWB – SHF1 – DNV – IEC 60332-3-22 – batch.no – dd/mm/yy – ****m
Specifications
Operating temperature normal
-40 – +80 [°C]
Temperature @ installation
-20 – +60 [°C]
Dielectric strength
DC 2kV for 1min.
Characteristic impedance
120 ± 15 [Ω @ 1MHz]
Conductor resistance
≤ 55 [Ω/km]
Resistance unbalance
≤ 5 [%]
Insulation resistance
≥ 1 [GΩ x km]
Attenuation
≤ 20.0
[dB/km @ 1MHz]
Min. bending radius installed
8 [x outer diam]
Min. bending radius @ installation
15
[x outer diam]
Norms
Halogenfree, max content corrosive and toxic gases
IEC 60754-1 & IEC 60754-2
Material properties, insulation and sheath
IEC 60092-360 (359)
Design and testing standards
IEC 61158-2
Flame resistance
IEC 60332-3-22 Cat.A
Flame retardant
IEC 60332-1-2
Smoke emission
IEC 61034-2
Oil and fuel resistant
IEC 60811-2-1
IRM 902
23ºC / 7 days, 70°C / 4h
UV-resistant
UL 1581 (300H)
Certification
DNV
Pairs | Outer diam. [mm] | Weight [kg/km] | Art. no. |
---|---|---|---|
1 x 2 x AWG22/7 GSWB | 9.8 ± 0.5 | 2040006 | |
2 x 2 x AWG22/7 GSWB | 9.8 ± 0.5 | 2040005 | |
4 x 2 x AWG22/7 GSWB | 10.3 ± 0.5 | 124 | 2040003 |
1 x 2 x AWG22/7 TCWB | 9.8 ± 0.5 | 2040025 | |
2 x 2 x AWG22/7 TCWB | 9.8 ± 0.5 | 2040026 | |
4 x 2 x AWG22/7 TCWB | 10.3 ± 0.5 | 2040027 |
Updated
Date | Rev. | Description |
---|---|---|
08.02.2022 | 0 | Created |